Bathroom zones: what goes where under BS 7671

BS 7671 treats rooms with a bath or shower as special locations. Section 701 divides the space into zones based on how likely equipment is to get wet, and sets what can go in each one.

The zones

ZoneWhereWhat it means
Zone 0Inside the bath or shower trayOnly equipment made for it, at least IPX7, and separated extra low voltage of no more than 12V AC
Zone 1Directly above the bath or tray, up to 2.25m from the floorAt least IPX4. IPX5 where jets of water may be used for cleaning
Zone 2The 0.6m band beyond zone 1, up to 2.25mAt least IPX4. IPX5 where jets of water may be used for cleaning
Outside the zonesThe rest of the roomNo zone IP rating, but the room's other rules still apply

Sockets and shaver points

Standard 13A sockets are not allowed within 3m horizontally of the boundary of zone 1. That rules them out of most hotel and HMO bathrooms. A shaver supply unit made to BS EN 61558-2-5, such as the BG 940, is the exception: it can be installed in zone 2 where it is unlikely to be hit directly by shower spray.

RCD protection

Every circuit serving the location needs 30mA RCD protection, including lighting and the shower circuit. This is a common gap when an older room is only partly rewired.

Switches

Keep light switches outside the zones, or use a ceiling pull cord. Inside zones 1 and 2 only switches that are part of a SELV circuit are allowed.

This note is a summary for planning and ordering. Design and certification of the installation remain with the qualified electrician responsible for the work.